• Personal advice
  • Installed within 6 weeks
  • Affiliated with SGZE
  • Certified company
Carefree enjoyment of the sun
Free consultation

Backup power from a home battery: keep the lights on when the street goes dark

Including a calculator: see how long your house would last

Thuisbatterij met noodstroomfunctie tijdens een stroomstoring
Thuisbatterij met noodstroomfunctie tijdens een stroomstoring
Thuisbatterij met noodstroomfunctie houdt stroom terwijl de hele straat in het donker zit

The Netherlands has one of the most reliable power grids in Europe. On average a household here is without power for only about 20 minutes a year because of an outage (21.7 minutes in 2025, according to Netbeheer Nederland). Sounds good, right? But that average does not tell the whole story. Most households have no outage at all in a year, and those who do have one sit in the dark for well over an hour on average. Never at 3 in the morning, when nobody notices. Always exactly during dinner, the penalty shoot-out or that one important video call with your boss.

And then comes the surprise: your solar panels do nothing either. A roof full of sun, a house without power. How can that be?

In this blog we explain it to you. Why your inverter stops straight away during a power outage, and how emergency power from a home battery simply keeps your lights, wifi and a cold fridge going. You will also read the difference between emergency power (one separate circuit in your meter cupboard keeps working) and backup (your whole home keeps working), because those are two different solutions. Including a calculator, so you can see right away how long your home keeps going while the rest of the street looks for candles.

Request a consultation

 

Why your inverter stops during a power cut (and why that is a good thing)

First the bad news. When the power goes out, an ordinary inverter switches itself off almost immediately, within two seconds at the latest. Not because it is broken. It does exactly what it is supposed to do: nothing at all.

This is called anti-islanding protection. It is mandatory under the Dutch Netcode elektriciteit and the European standard NEN-EN 50549-1. Since April 2021 no new or replaced inverter goes onto the grid without a certificate under that standard. Every inverter on the power grid has this protection. So your inverter is not lazy. It is obedient. Switching it off is not possible. And believe us: you would not want to either. Below you can read why.

Islanding: sounds like a holiday, is not one

Without that protection your installation would keep putting power onto the grid while the whole neighbourhood sits in the dark. Your home then unintentionally becomes a small power island. Hence the name island mode. Sadly: no palm trees, no cocktails, but a danger to life. The only island nobody books a ticket for.

The engineer from the grid operator who comes to repair the fault assumes the cable is dead. If your inverter is still putting voltage on it, that engineer is suddenly working on a live cable. You would not wish that on anyone.

It can also damage your appliances and the grid the moment the power returns and is no longer in step with your system. So the rule is hard and simple: no grid, no inverter. Full stop.

Yet there is also a good island. That is exactly what emergency power and backup do, and the secret is in the order: first physically disconnect your home (or part of it) from the grid, and only then make your own voltage. That way there is never power on the cable the engineer is working on. The same island, but with the barrier down.

How you do keep power: a home battery with a backup function

The solution is not in the panels. They cannot help it. They just work here. The solution is a home battery with a hybrid inverter with a separate emergency power output, called EPS in the trade (Emergency Power Supply). Or, one step further, a backup box that takes over your whole home. Two different solutions, two different price tags. We explain the difference below.

The clever part is the disconnecting. During an outage the system automatically disconnects your home, or a separate part of it, from the public grid. Your home is really saying, very politely: "I'll take over for a moment." This creates a deliberate and safe little island: the good island from above. No more power goes onto the grid, and within your walls the battery simply powers your most important appliances. You have power, the engineer is safe. Everybody happy.

Is the grid back? Then the system first waits about a minute, until voltage and frequency are stable again. After that it neatly reconnects itself and continues charging the battery.

Emergency power or backup: what is the difference?

Emergency power is the entry level. One separate emergency power circuit in your meter cupboard keeps working: fridge, lighting, wifi and central heating boiler. The hybrid inverter has its own emergency power output for this. The rest of the house stays dark during the outage, but the most important things keep running. This is part of most hybrid systems we install.

Backup is the complete version. A transfer switch on your main connection disconnects your whole home from the grid, and the battery and solar panels take over everything. Every circuit keeps working, as long as your total consumption stays within the power of your system. You switch off the heat pump and the charging station during an outage, or you let them switch off automatically. You need a backup box or system controller for it, and usually a larger battery.

An emergency power socket is the lightest form. Our plug-in HYXi Halo has one: one socket on the battery itself stays live, up to 3,000 watts. Your circuits in the meter cupboard do not. Handy for the fridge and the router, not for the whole household.

And a UPS? That is something else again: an emergency supply without even one millisecond of interruption, for a computer or server. Our hybrid inverters switch over so fast (within 4 to 20 milliseconds) that your PC and router do not notice a thing. In the market that is called 'UPS level'.

LevelWhat keeps working during an outageSwitch-overPowerIn our range
Emergency power socketOne socket on the battery itself. You plug appliances into it yourself; your circuits in the meter cupboard stay off.Automatic, within 20 ms1,500 W (base) up to 3,000 W (with extra module)HYXi Halo (plug-in)
Emergency power (emergency power circuit)One or a few circuits in your meter cupboard: fridge, lighting, router, central heating boiler. The rest of the house is dark.Within 4 to 20 msSingle-phase 3 to 8 kW, three-phase up to 10 kWSolis S6 hybrid inverter, HYXi hybrid H series
Backup (whole home)Your whole home, as long as consumption stays within the power of the inverter and battery. Large consumers off or prioritised.Per brand: HYXi a few milliseconds, Enphase within 120 ms, SolarEdge a few secondsThe power of your system, for example 3.84 kVA per Enphase IQ Battery 5P or 63 A per phase with HYXiEnphase IQ Battery 5P with IQ System Controller 3, SolarEdge Home Hub with Home Backup Interface, HYXi All-in-One

The systems we install, per level:

  • Emergency power socket: the plug-in HYXi Halo. You start with 3 kWh and expand up to 18 kWh in steps of 3 kWh. With only the main unit the emergency power socket delivers 1,500 watts, from one expansion module 3,000 watts, automatically within 20 milliseconds. Handy for the fridge, router and lighting; your meter cupboard stays without power.
  • Emergency power circuit: the hybrid inverters from Solis and HYXi. The single-phase Solis S6 switches over within 4 milliseconds, the three-phase S6 of 10 kW within 10 milliseconds and then keeps up to 10 kW of emergency power available. The HYXi H series does it within 10 milliseconds. The installer puts one or a few circuits in your meter cupboard on the emergency power output.
  • Backup of your whole home: Enphase IQ Battery 5P with the IQ System Controller 3 (automatic transfer switch on your main connection, within 120 milliseconds, 80 A per phase), SolarEdge Home Hub with the Home Backup Interface (your whole home or selected circuits, switch-over in a few seconds) and the HYXi All-in-One, where inverter, battery and transfer switch sit in one cabinet: 10 to 25 kWh, an inverter that grows from 6 to 15 kW and 63 A per phase for your whole meter cupboard.
Adviseur van Dijkman Zonne-energie bekijkt samen met de klant de zonnepanelen op het dak

Step by step: what happens when the power fails

  1. The system notices within milliseconds that the grid has gone. Faster than you can say "hang on, the wifi is down".
  2. An automatic switch disconnects your emergency power circuit from the grid, or with backup your whole home. With an emergency power circuit that switch is in the inverter itself; with backup it is a transfer switch or backup box at your main connection. Nothing is fed back.
  3. The inverter and the home battery take over and power that circuit, or your whole home.
  4. Your fridge, lighting, router and central heating boiler simply keep running. With SolarEdge they come back on after a few seconds. Your fridge does not even notice.
  5. Is the grid back? Then the system first waits about a minute, until voltage and frequency are stable again. After that it switches back to the grid by itself (with some systems you notice a second short hiccup) and simply recharges the battery.

You have nothing to do. No plugs to move. No torch between your teeth. No panic at the meter cupboard.

 

Which appliances go on the backup circuit?

If you choose emergency power, you do not put your whole house on the battery. You do not need to either. You choose a separate circuit with the things that really matter:

  • Fridge and freezer (about 150 watts): nobody wants a thawed freezer.
  • LED lighting (about 60 watts): candles are cosy, until you knock three of them over.
  • Wifi router and modem (about 15 watts): you can survive a power cut, but not one without wifi.
  • Central heating boiler (about 100 watts): even a gas boiler needs electricity. This keeps the house warm.
  • Television (about 80 watts) and charging phones and laptops (about 60 watts).

What you usually do not put on it: the hob, the heat pump and the charging station. The charging station alone eats a whole home battery for breakfast: charging at 11 kW drains a 10 kWh battery in less than an hour. And yes, sadly the 1400 watt coffee machine too. It drains your battery as if it were nothing. Life is hard, we know.

Do you choose backup of your whole home? Then those large consumers do stay connected, but you switch them off during an outage, or you let them switch off automatically. That way you save your battery for the things that really matter.

Monteur bevestigt zonnepanelen op het dak tijdens de installatie

Calculator: how long would your home battery last?

Tick what has to keep running at your home, choose your system and your battery size and see right away how many hours of emergency power you have. Feel free to play with it. The coffee machine in particular is instructive.

What has to keep running?

What do you use now and then during the outage?

These run for minutes, not hours. We count them per use.

Which system?

How large is your home battery?

How full is your battery when the outage starts?

Your result

Indication based on average power ratings and 85% usable capacity (depth of discharge and inverter losses). Actual consumption differs per household and appliance. Power ratings and battery sizes as stated by the manufacturer.

Switch-over time: you usually do not notice a thing

Good news for the divas among your appliances. Most hybrid inverters we install switch over within 4 to 20 milliseconds. A blink of an eye takes longer. So your computer (faints at the smallest voltage dip) and your router simply keep running. In the market that is called 'UPS level', after the UPS (Uninterruptible Power Supply, the emergency supply from server rooms). A real UPS switches without any interruption and also filters out voltage dips; a hybrid inverter does not do that, but for a PC and router UPS level is more than enough in practice.

The exception is SolarEdge. The Home Hub with Home Backup Interface needs a few seconds, after which everything starts up again. Your fridge and central heating boiler do not lose sleep over that; your PC restarts. With a backup box for your whole home the switch-over time also differs per brand, so get good advice.

Switch-over time per system in milliseconds The single-phase Solis S6 switches over within 4 milliseconds, the three-phase Solis S6 and the HYXi H series within 10, the HYXi Halo within 20 and Enphase within 120 milliseconds. A blink of an eye takes about 150 milliseconds. SolarEdge with Home Backup Interface needs a few seconds and falls outside the scale. Switch-over time during a power outage In milliseconds. Everything left of the orange line is faster than a blink of an eye. blink of an eye, about 150 ms Solis S6 hybrid inverter, single-phase < 4 ms Solis S6 hybrid inverter, three-phase < 10 ms HYXi hybrid H series < 10 ms HYXi Halo (socket) 20 ms Enphase IQ System Controller 3 120 ms SolarEdge Home Hub with Home Backup Interface a few seconds (outside the scale) 050100150 ms
Switch-over times according to manufacturer documentation (September 2026). With a backup box for the whole home the time can differ per configuration.

The secret weapon: your battery charges again during the day

A standalone backup battery runs empty at some point, and then it stops.

With solar panels and a home battery it is different. If the failure lasts longer and the sun is out, your panels simply charge the battery again during the day, inside your own safe island. The sun sends no invoice. That is how you get through a longer power cut: you watch a film in peace while the neighbour empties his freezer.

One piece of small print: this works with hybrid systems, where your panels are on the same inverter as the battery, and with systems that form an island grid themselves, such as Enphase. When the battery is full, the system turns your panels down for a moment by itself. Do you have a separate battery next to an existing inverter? Then ask whether that inverter keeps running in island mode. Not every system can do that.

Woning met zonnepanelen op het dak die overdag de thuisbatterij bijladen

What should you look out for?

  • Not every home battery has an emergency power function. Some only switch over manually. During an outage plug-in batteries power at most an emergency power socket on the device itself; our Halo does that automatically, up to 3,000 watts, but your meter cupboard stays without power. If you want your circuits to keep working, you need a hybrid inverter with an emergency power output, or a backup box for your whole home. So ask about it explicitly.
  • For emergency power you need a separate emergency power circuit. A certified installer puts it in your meter cupboard. If you choose backup, there is no separate circuit, but a transfer switch or backup box on your main connection.
  • This is not a job for a Saturday afternoon. A YouTube video is not an installation diploma. Safely disconnecting from the grid has to meet the requirements of the grid operator and the installation standard NEN 1010. One detail that shows why: in island mode the system has to connect neutral to earth, otherwise your residual current device does not work. That only goes well when it is installed correctly. Have it done by a professional.
  • Mind single-phase or three-phase. A single-phase inverter only powers circuits on its own phase, and three-phase appliances such as a heat pump, hob or charging station need a three-phase backup. With a three-phase connection the configuration determines which circuits you can back up; some three-phase systems deliver only part of the power per phase.
  • Set an emergency power reserve. A battery that works hard during the day for your own consumption or for dynamic prices is often almost empty in the evening. Exactly at the moment the outage comes, because that is how it goes. With a reserve of, for example, 20 to 30 percent you always keep a floor. All systems we install have that setting; with Enphase you can even reserve 100 percent.
Monteur van Dijkman Zonne-energie geeft een duim omhoog op het dak

And then there is 2027

Net metering ends on 1 January 2027. From then on, using or storing your own solar power is the norm, which means the home battery is too.

See emergency power as the bonus with your home battery. You buy the battery to use more of your own solar power, and for a limited extra cost (a separate circuit and some installation work in the meter cupboard) you get the certainty of power during an outage on top. Two birds with one stone. And you do not even have to throw. Do you want your whole house behind a backup box? Then that is a larger investment. Our adviser works out both for you. Also read our blog about the end of the net metering scheme in 2027.

Frequently asked questions about emergency power and backup with a home battery

Do I automatically have power during a power outage with solar panels?
No. An ordinary inverter is required to switch off during an outage because of the anti-islanding protection. Only with a home battery with an emergency power or backup function do you keep power.

What is the difference between emergency power and backup?
With emergency power one separate circuit in your meter cupboard keeps working: fridge, lighting, wifi and central heating boiler. The rest of the house is dark. With backup a transfer switch on your main connection disconnects your whole home from the grid and the battery and solar panels take over everything. Backup needs a backup box or system controller and usually a larger battery.

Does emergency power also work at night?
Yes, as long as there is charge in the battery. So set an emergency power reserve, so that something is always left in the evening. During the day your solar panels recharge the battery.

Can I put my whole house on emergency power?
Yes, that is called backup. A transfer switch on your main connection disconnects your whole home from the grid. The power of the inverter and battery does have to match your consumption, and you switch off large consumers such as the heat pump and the charging station during an outage.

How fast does the system switch over?
Most hybrid inverters switch over within 4 to 20 milliseconds; you do not notice that. SolarEdge needs a few seconds, after which everything starts up again.

Does a plug-in home battery have emergency power too?
Only through an emergency power socket on the battery itself. Our HYXi Halo switches it on automatically, within 20 milliseconds, up to 3,000 watts. Your circuits in the meter cupboard stay without power.

Want to know what is possible in your meter cupboard?

Our advisers look at your consumption, your meter cupboard and your solar panels. Then we work out which home battery with emergency power or backup suits your situation. No obligation, with coffee. That always works at our place. Contact us.

Mark, adviser at Dijkman Zonne-energie
Mark
9.1/10 | 2064 reviews
J.Boerman 9

“De installalatie keurig volgens offerte en tijdsplanning snel en vakkundig aangebracht.”

Interested in a home battery with emergency power or backup?

Request a consultation

Mark is an adviser at Dijkman Zonne-energie and knows everything about home batteries, emergency power and backup. He is happy to work out which solution suits your home: an emergency power circuit or a backup of your whole home.

Mark, adviser at Dijkman Zonne-energie
Mark

Want to know more about smart energy solutions?

Home battery

Read more

Types of charging stations: which one should you choose?

In this blog we explain which types of charging stations there are and which features suit your situation best.

Read more

The advantages of a home battery: optimise and save

A home battery has plenty of advantages that help you optimise and save. Read more in this blog.

Read more